How often does test and tag need to be done?

Test and Tag retest frequencies vary by State in Australia. Below is a convenient summary of the requirements across Australia.
Type of Environment and / or Equipment
Class of Work QLD |
NSW, ACT, TAS, SA, NT, VIC and WA |
QLD |
Factories, workshops, places of work or repair manufacturing, assembly, maintenance, fabrication |
6 months |
|
Environment where the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment |
12 months |
|
Environment where the equipment or supply flexible cord is NOT subject to flexing in normal use OR is NOT open to abuse OR is NOT in a hostile environment |
5 years |
|
Residential type areas of hotels, residential institutions, motels, boarding houses, halls, hostels, accommodation houses and the like |
2 years |
|
Equipment used for Commercial Cleaning |
6 months |
|
Hire Equipment |
Inspection prior to hire 3 monthly Test and Tag |
|
|
|
|
Construction Work QLD |
|
3 monthly |
Manufacturing Work QLD |
|
6 monthly Single Insulated 12 monthly Double Insulated |
Service Work QLD |
|
Annual OR all circuits protected by RCD and RCD tested regularly |
Office Work QLD |
|
5 Yearly OR all circuits protected by RCD and RCD tested regularly |
Amusement Work QLD |
|
6 monthly Single Insulated 12 monthly Double Insulated |
Rural Work QLD |
|
Annual OR all circuits protected by RCD and RCD tested regularly |